NPRR424 Reactive Capability Testing Requirements for IRRs
ReasonIn order to perform effective testing and evaluation, this NPRR proposes new parameters for IRR lagging and leading tests. IRR lagging tests are to be conducted when the IRR is generating at or above 60% its seasonal High Sustained Limit (HSL). Conducting lagging tests at this level will allow IRRs a more reasonable opportunity to complete lagging tests. IRR leading tests are to be performed when the IRR is generating below 35% of its seasonal High Sustained Limit (HSL), we believe that conducting leading tests at this level will provide better evaluation of the IRRs ability to respond to voltage issues.
Created2011-11-17
Approved2012-04-17
Sections Affected
8.1.1.2.1.4
Summary
This Nodal Protocol Revision Request (NPRR) defines the reactive capability testing requirement for Intermittent Renewable Resources (IRRs).
Timeline
- Nov 2 '11
- Nov 17 '11
-
Dec 15 '11
PRS PRS MeetingPRSRecommended for Approval Recommended for approval Amended by the Dec 8 '11 ERCOT comments“To recommend approval of NPRR424 as amended by the 12/8/11 ERCOT comments” — Passed→ PRS IA Review
-
Jan 19 '12
PRS Protocol Revision Subcommittee (PRS) MeetingPRSRecommended for Approval Recommended for approval Forwarded → TAC“To endorse and forward the 12/15/11 PRS Report as revised by PRS and the Impact Analysis for NPRR424 to TAC” — Passed→ TAC Consideration
- Jan 30 '12
-
Feb 2 '12
TAC Technical Advisory Committee (TAC) MeetingTACRecommended for Approval Recommended for approval“To recommend approval of NPRR424 as recommended by PRS in the 1/19/12 PRS Report” — Passed→ ERCOT Board Consideration
- Feb 15 '12
-
Apr 16 '12
Listed without action at 1 meeting
-
Apr 17 '12
BOARDEmail Vote / Unlisted MeetingBOARDApproved Recommended for approval“To approve NPRR424 as recommended by TAC in the 3/1/12 TAC Report” — Passed