ERCOT·WATCH Search ercot.com  ⌕
NPRR #1106 · Revision Request

NPRR1106  Deployment of Emergency Response Service (ERS) Prior to Declaration of Energy Emergency Alert (EEA)

Approved Urgent sponsor ERCOT posted 2021-11-04 ercot.com
ReasonAddresses current operational issues; Market efficiencies or enhancements; Regulatory requirements
Created2021-11-10
Approved2021-12-16
Sections Affected
2.13.14.36.5.9.4.16.5.9.4.26.5.9.4.38.1.3.1.3.1and 8.1.3.1.3.2
Summary
This Nodal Protocol Revision Request (NPRR) revises the Protocols to allow for the deployment of ERS prior to the declaration of an EEA when Physical Responsive Capability (PRC) falls below 3,000 MW and is not projected to be recovered above 3,000 MW within 30 minutes following the deployment of Non-Spin.
Timeline