ERCOT·WATCH Search ercot.com  ⌕
NPRR #1094 · Revision Request

NPRR1094  Allow Under Frequency Relay Load to be Manually Shed During EEA3

Approved sponsor Oncor posted 2021-09-01 ercot.com
ReasonAddresses current operational issues
Created2021-09-16
Approved2021-12-16
Sections Affected
6.5.9.4.2
Summary
This Nodal Protocol Revision Request will allow a Transmission Operator (TO) and a Transmission and/or Distribution Service Provider (TDSP) to manually shed Load connected to under-frequency relays during an Energy Emergency Alert Level 3 (EEA3) if the affected TO can meet its overall Under-Frequency Load Shed (UFLS) requirement in Nodal Operating Guide Section 2.6.1, and its Load shed obligation under Nodal Operating Guide Section 4.5.3.4.
Timeline