ERCOT·WATCH Search ercot.com  ⌕
NOGRR #227 · Revision Request

NOGRR227  Add Phasor Measurement Recording Equipment Location for Main Power Transformer for Intermittent Renewable Resource (IRR)

Approved sponsor ERCOT posted 2021-05-19 ercot.com
ReasonAddresses current operational issues
Created2021-06-03
Approved2021-10-07
Sections Affected
6.1.3.3
Summary
This Nodal Operating Guide Revision Request (NOGRR) allows for single phase current magnitude/angle data for an interconnected Intermittent Renewable Resource (IRR) over 20 MVA to be taken from either side of the main power transformer where turbines exist on a feeder(s) that were aggregated to two or more IRRs.
Timeline