NOGRR #62 · Revision Request
NOGRR062 Require Voltage Ride-Through Capability for IRRs
ReasonThis NOGRR is being proposed for the following reasons: Due to the expected IRRs to be placed in service over the next few years, lack of VRT capability could pose ERCOT reliability issues in the event of voltage excursions. Concern of sudden voltage changes causing tripping of units without VRT capability. Additionally, although the VRT study indicated there was no need to retrofit existing Wind-powered Generation Resources to add VRT capability, the concern remains if more units without VRT capability are placed in service, especially in west Texas where many existing WGRs do not have VRT capability.
Created2011-03-10
Sections Affected
2.9.1
Summary
This Nodal Operating Guide Revision Request (NOGRR) proposes a requirement for Voltage Ride-Through (VRT) capability for new IRRs
Timeline
- Mar 3 '11
-
Mar 10 '11
ROS ROS MeetingROSRecommended for Approval Recommended for approval Forwarded → TAC“To recommend approval of NOGRR062 and to forward NOGRR062 and the Impact Analysis to TAC” — Passed
-
Apr 7 '11
TAC TAC MeetingTACApproved Recommended for approval“To approve NOGRR062 as recommended by ROS in the 3/10/11 ROS Report”
-
—
Posted since the last meeting